Effect of depth and insulation of a fruit cold storage plant floor on heat exchange with the ground

Warianty tytułu

Języki publikacji

EN

Abstrakty

EN
The method of 3-dimensional, transient heat transfer calculation through partitions touching the ground (floor and walls) was presented. The effect of a fruit cold storage plant floor depth and thermal insulation on heat gains during storage period was analysed. Results of calculations show the great disadvantage of partly underground location and lack of floor insulation of cold storage in comparison with traditional fruit stores. Insulating the floor with foamed polystyrene 10 cm thick reduces total heat gains during the whole cold storage season by as much as about 40% and several times lowers demand of necessary power of cold-storage plant at the beginning of storage period.

Wydawca

-

Rocznik

Tom

06

Numer

1

Opis fizyczny

http://www.ejpau.media.pl/series/volume6/issue1/engineering/art-01.html

Twórcy

autor
  • University of Agriculture in Krakow, Al.Mickiewicza 24-28, 30-059 Krakow, Poland
autor
autor

Bibliografia

  • Bieda W., Nawalany G., 1998. Stan przechowalni owoców i kierunki poprawy ich wartości użytkowej w rejonach sadowniczych Pogórza [Thermal state of fruit storage base in the fruit-growing regions of Foothills and ways of their improvement]. Scientific Papers of Agr. University of Wroclaw, ser. Conferences, NR 338. 67-74 [in Polish].
  • Drozdowicz M., 1966. Wykorzystanie naturalnych warunków klimatycznych w przechowalnictwie płodów ogrodniczych [Utilisation of natural climatic conditions in storing of crops]. Zakład Wydawnictw CRS, Warszawa [in Polish].
  • Drozdowicz M., 1969. Budowa przechowalni i przechowywanie owoców przez producentów [Construction of storage and storing of fruits by producers]. Zakład Wydawnictw CRS, Warszawa [in Polish].
  • EN ISO 13370, 1998. Thermal performance of buildings – Heat transfer via the ground – Calculation methods, CEN.
  • Esdorn H., Fortak H., Jahn A. (1985), Developing of Test Reference Year (TRY), Energy consumption in residential houses. Verlag TÜV-Rheinland, Köln [in German].
  • Gdula, S. J., 1984. Przewodzenie ciepła [Heat transfer]. PWN, Warszawa [in Polish].
  • Nawalany G., 2001. Wymiana ciepła pomiędzy zagłębioną przechowalnią owoców a gruntem oraz możliwości jej optymalizacji [Heat exchange between partly underground located fruit storage and possibility of it’s optimisation]. Typescript, AR Kraków [in Polish].
  • PN-91/B-02020. Ochrona cieplna budynków. Wymagania i obliczenia [Thermal protection of buildings. Requirements and calculations]. Polish Normalisation Committee, Warszawa [in Polish].
  • PN-EN ISO 6946, 1999. Opór cieplny i wskaźniki przenikania ciepła. Metoda obliczeń [Thermal resistance and thermal transmittance – Calculation method]. Polish Normalisation Committee, Warszawa [in Polish].